How do I turn my mixing valve into watts?
How do I turn my mixing valve into watts?
To adjust the setting of the valve, loosen locking cap screw with hex wrench, see Figure 2. Cap must be lifted 1/4” to adjust temper- ature. To increase the tem- perature, turn counterclockwise. To decrease temperature turn clockwise.
How to adjust a Thermostatic Mixing valve?
To adjust the temperature supply remove the plastic cap on top of the valve and adjust with a close fitting spanner. To increase the temperature turn anti-clockwise To decrease the temperature turn clockwise To set the valve to a maximum recommended mixed water temperature, see table below.
What is the maximum pressure for MMV Watts?
The MMV is available with either union thread (-UT), union solder (-US), CPVC, Quick-Connect (-QC) or PEX end connections. Maximum pressure is 150 psi (10.55 bar). For product-specific approval information, please refer to the product’s specification sheet or ask a Watts representative.
How does the MMV series water valve work?
The MMV series uses a double throttling design to control both the hot and cold water supply to the mixed outlet. The superior flow characteristics of this valve provide accurate temperature control (+/-3°F) with low pressure drop across the rated flow range.
What should the temperature be for a MMV mixing valve?
The MMV series can be set to any temperature between 80°F and 120°F with flow rates as low as 0.5 gpm and as high as 12 gpm. This mixing valve series is listed under ASSE 1017 for hot water source applications, ASSE 1069 for end use fixture fittings and ASSE 1070 for single or multiple fixture applications.
Is the lfmmv-Watts a tempered water valve?
This mixing valve series is listed under ASSE 1017 for valves used in hot water source applications, ASSE 1069 for single-pipe, tempered water applications, and ASSE 1070 for valves used in individual or multiple fixture applications, and also listed IAPMO cUPC.